联系我们 | 工程业绩 | 技术专栏 | 下载中心 | English  
 
 
  产品列表
 代理产品
      SSD 590直流调速器
      西门子自动化系列
      三菱、富士全系列
      欧陆调功器,可控硅
      欧陆温控器,记录仪
      施耐德固态继电器
      特价促销产品
      配件(parker 590)
 系统成套
      PLC控制柜
      直流调速柜
      交流变频柜
      自动化控制系统
 技术服务
      590直流调速器维修
      代理品牌变频器维修
      PLC编程及技术培训
      触摸屏编程组态
 
 
 
 
   
 
 
欧陆图像DAQ记录仪

Click here for more information.


E57766
Data Visualization and Management, Touch Sensitive Graphic Display, Archiving, OPC Server
Bridge 5000, Batch 5000, Review 5000, Report 5000
Go ONLINE via Ethernet to a 5100V Recorder using the Chessell Bridge 5000 Software.
Connections Made Easy?- Modbus Master & Slave Digital Communications - modbus/TCP or Serial modbus/RTU

 
Inputs
6-48
6-12
6
Graphic Display
12.1" (307.34mm)(SVGA)
TFT color LCD
5.5" (139.7mm)(1/4 VGA)
TFT color LCD
5" (127mm)(1/4 VGA)
STN color LCD
User Interface
Touch Sensitive Screen
Touch Sensitive Screen
Touch Sensitive Screen
Communications
Ethernet/Serial
Ethernet/Serial
Ethernet
Modbus TCP
Modbus RTU
 
ASCII
 
Relay Outputs
3-27
3 - 12
1
Annotation
Datalogging
Archive Media
Type II PC Card or 3.5" Disk
Type II PC Card or 3.5" Disk
3.5" Disk
Auditor Features
 
Batch
  
Custom Screens
 
Remote Viewing
Mathematics
Totalizers, Timers & Counters
SNTP
PC Configurable
Go ONLINE via Ethernet to a 5100V Recorder using the Chessell Bridge 5000 software and see how easy it is to remotely monitor, navigate and configure any of the Chessell 5000 Series Recorders. Here is what you need to do.
1) Get a copy of the Chessell Bridge 5000 Software and install it on your Windows PC. Click here to download a copy if you don't already have one. File size is 17MB.
2) Go to start/Programs/Eurotherm/Bridge 5000 to start the Chessell Bridge software. Enter 149.121.12.20 for the Host Name, Engineer for User Name and uncheck the Password required if checked box. Click on Start. In less than a minute the Chessell Bridge software connects to a 5100V displaying real-time and historical data.
April 2003 - V3.0 Recorder New Features
Modbus Master Digital Communications - modbus/TCP or serial modbus/RTU

Eurotherm have introduced an advanced new communications feature to its Series 5000 Data Acquisition Products. This will allow process data from multiple linked plant instruments, including temperature controllers, programmable controllers and other devices, to be displayed and recorded at a central location. Using standard Ethernet modbus/TCP and serial modbus/RTU connections, any Series 5000 recorder with the Master Communications feature will be able to read/write, log and display data from up to 16 slave instruments.

Eurotherm say that this is the first time that the company's data acquisition products have had this type of master data communications feature, and it will open up many new application areas for the highly successful Series 5000 family. Master Comms will, for instance, allow full control system integration in heat treatment systems based on interconnected PID temperature controllers, new control functionality to be added to existing 'legacy' systems without extensive modification, or more generally, increased system I/O without heavy investment or downtime. In addition, the 5000 Series are designed for compliance with 21 CFR Part 11 and the unit can be used as a Master device to assist in the FDA validation of plant legacy equipment.

The 5000 Series also provide 'Talk Through' communication. This will allow serially connected instruments to be configured over the Ethernet link, using the Master Series 5000 recorder (including both blind and display versions) as the gateway. As the system uses Modbus, data may be received from or sent to any third party Modbus serial or Modbus TCP device. Coupled with custom visualisation, control and data recording, such networks may also act as small SCADA solutions.

The Master Comms package incorporates a number of powerful operational features, which give it exceptional functionality and ease of use. It will, for instance auto detect individual slave devices on a selected network, and allow each to be individually configured remotely. Pre-defined profiles, along with a 3rd party profile, are supplied for support of a wide selection of instrumentation, as are device-specific diagnostics tools. These include the ability to reset to default &#118alues on loss of data or communications error flags.

With Master Comms, the Series 5000 instrument will still retain full data recording functionality, including trending and remote batch control. It will also, through its standard Auditor feature, be capable of displaying, transferring and managing secure, tamperproof data. This will in many cases allow FDA 21CFR Part 11 compliance; including electronic signing and authorising, time-stamped audit trails and other security related features.

While the Master Comms feature is able to communicate with almost any 3rd party slave device capable of using Modbus protocols, it does have an 'in-built' data base covering a wide range of proprietary Eurotherm instruments. These include all other data acquisition instruments within the Series 5000 family, 4000 Series recorders (paper and graphical) and 2000 Series temperature and process control products such as the models 2216/08, 2404/08/16, 2500 and 26/2704.

Product
Max Slave
Devices
Max Input
Channels
Cyclic Write
Output
On Demand
Write Outputs
5180V
16
96
48
48
5100V
16
48
48
48
5000B
16
96
48
48
 
Additional Math Functions
O2 Correction, Timestamp, Rate Of Change, Relative Humidity, Zirconia Probe, Log10, Loge, ex, Modulus, Channel Min, Channel Max, Channel Average
User Screens
Addition of operator and event buttons.
Jobs
Alarm Acknowledge added

The 5000 Series units all offer unrivalled input accuracy with a 125mS total sample rate for up to 48 channels. At the heart of the design is a leading edge Power PC, 32-bit RISC processor.

Ethernet networking has become the recognized standard for high-speed data transmission within large plants and beyond. Series 5000 incorporates FTP (file transfer protocol) and modbus/TCP -- as a Master or Slave -- via its standard Ethernet communications, enabling the archiving and integration of data into any plant-wide data network.

Data visualization needs to be presented in the most easily interpretable format to the operator. In addition to the standard displays of bar, chart and numeric formats, custom displays (plant mimics*) can be created for the series 5000 recorders. The advanced software environment allows for display creating images that are both static, and have moving elements.

A Touch Sensitive Screen coupled with a ?VGA or SVGA TFT color LCD display provides excellent display capabilities. The Series 5000 features a simple to use WindowsTM style system configurator, that is mirrored in the PC-based configuration program, allowing ease of transition between either method of set up.

Bridge 5000 is PC software that provides remote access to the series 5000 recorders, via Ethernet. Using the software, the operator sees real time data from the recorder. Navigation of the operator interface on the PC is identical to that of the unit, using a mouse to point and click where the recorder uses a touch screen.

Archiving is available on a choice of media, either 3.5?floppy diskette, or PC card*, with up to 1 Gbyte of memory. Data is transferred from the instrument抯 non-volatile memory in hourly, daily or weekly files. Data can be archived at a rate which matches the units?high input scan rates ?8Hz. All data is stored in tamper-proof binary format that can be used for long term record processing.

The Batch 5000 feature* offers batch functionality based on the requirements of FDA title 21 CFR part 11. The capabilities of this feature include: entering of six batch fields (e.g. current operator, batch number, customer name, order number, etc.), batch mode (start/stop or continuous).

OPC server capability (OLE for process control) defines the standard by which instrumentation can be integrated into modern automation/business systems. This enables Series 5000 recorders to be incorporated into the software system of your choice, without the need to assemble costly new drivers.

Use of the Eurotherm custom chip set ensures high quality I/O. One A/D converter per channel negates the need for relays or solid state switching, providing continuous measurement and parallel sampling for each input. High noise rejection and isolation (250 volts channel to channel and channel ground) ensures measurement integrity in the harshest of environments. This high accuracy data acquisition occurs at an input scan rate of 8Hz (all channels scanned every 125ms).
* Not Available on 5100e

点击数:1216  录入时间:2012/2/8 【打印此页】 【返回  
 
 

地址:上海市九亭久富开发区龙高路356号 电话:021-35500900 传真:021-53700008
版板所有© 上海荟格企业 沪ICP备07019868号